Flocorp MEMFlo™ MFT2 flow transmitter accurately calculates and outputs the flow rate. Compatible with any MEMFlo variable area flow meter, MFT2™ combines FLO-CORP’s time-proven variable area technology with a high tech processor and solid-state circuitry.
Flocorp MEMFlo™ MFT2 Universal 2-Wire Flow Transmitter |
Each device includes an analog output that can be configured for 0-5 VDC, 0-10 VDC, or 4-20 mA current loop. Typical applications include pump flow output, compressed air consumption, cooling flow monitoring, steam flow usage/optimization and combustion gas metering.
Flocorp MEMFlo™ MFT2 Features and Benefits
- Non-contact sensor electronic
- Electronic signal conditioning circuit
- 3 output modes: 4-20mA, 0-5 VDC or 0-10 VDC
- Proportional analog output - two-wire, 4-20mA
- Designed to slip over any standard measuring tube
- Pre-calibrated from the factory for fast installation and start-up
- Optional Epoxy Coated Aluminum Enclosure for durable, rugged applications
Specifications
General | |
Process Temperature | F: -20º to 240º C: -29º to 116º |
Ambient Temperature | F: -20º to 158º C: -29º to 70º |
Environmental | Humidity: 0-90% non-condensing |
Accuracy | ±1% 0.25% rate |
Repeatability | ±0.10% rate |
Electrical | |
Power Requirements | 0.5 VDC Output 10-30 VDC @ 3 wire 0-10 VDC Output 12-30 VDC @ 3 wire 4-20 mA Output loop-powered, 12 VDC - 30 VDC - 2 wire |
Power Consumption | 25 mA maximum |
Analog Outputs | 0-5 VDC and 0-10 VDC into 10,000 Ohms minimum; 4-20 mA into 1000 Ohms maximum |
Resolution | 1:4000 |
Transmission Distance | 4-20 mA limited by cable resistance (4000’) 0-5 VDC 1000 feet (330m) maximum 0-10 VDC 1000 feet (300m) maximum |
Circuit Protection | Reverse polarity and current limiting |
Isolation | Inherently isolated from the piping system |
Transient Over-Voltages | Category 3, in accordance with IEC 64 |
Temperature Drift | 50 ppm/ºC (Max) |
Enclosure Rating | NEMA 4 (IP67) ; NEMA 7, Aluminum |